Sharp900 G4 1 – 3 kVA
The Sharp900 G4 1 – 3 kVA is an advanced UPS system featuring high-frequency online double conversion technology, DSP control, and active power factor correction. It ensures reliable power protection with a wide input voltage range, flexible charging, and effective software and hardware safeguards. The UPS offers quick charging, customizable settings via an LCD display, and multiple communication options. Optional accessories, including USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, and EPO function, provide enhanced functionality for diverse power needs.
Get Your Quote Now! Download the PDF here
Sharp900 G4 1 – 3 kVA:
- High frequency on-line double conversion technology
- DSP (Digital signal processing) control technology
- Active power factor correction (APFC), input power factor up to 0.99
- Output power factor 1.0
- Wide input voltage range (110V ~ 300Vac)
- Auto sensing frequency
- 50 / 60 Hz frequency conversion
- Digitally controlled charger, charging voltage and current configured by demands
- High charging current available (Max. 12 A)
- Cold start
- Rear ventilation design and variable speed fan
- Effective software and hardware protection
- Quick and stable charging, 90% capacity restored in 3h (standard model UPS)
- Linear derating in low voltage input reducing battery discharging times
- Advanced battery management (ABM)
- Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode
- Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
- Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function
MODEL | SHARP901 | SHARP902 | SHARP903 | ||||||||||||
Capacity | 1 kVA / 1 kW | 2 kVA / 2 kW | 3 kVA / 3kW | ||||||||||||
INPUT | |||||||||||||||
Rated voltage | 208/220/230/240Vac | ||||||||||||||
Voltage range | 110~ 176 Vac (linear derating between 50% and 100% load ); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%) | ||||||||||||||
Frequency range | 50/60 Hz±5 Hz (auto-sensing) | ||||||||||||||
Power factor | ≥0.99 | ||||||||||||||
Bypass voltage range | – 40% ~ +20% (settable) | ||||||||||||||
Rated input frequency | 50 Hz / 60 Hz (auto-sense) | ||||||||||||||
THDi | ≤5% | ||||||||||||||
OUTPUT | |||||||||||||||
Voltage | 208/220/230/240Vac(settable via LCD) | ||||||||||||||
Voltage regulation | ± 1% | ||||||||||||||
Frequency | 45~55Hz or 55~65Hz(synchronized range); 50/60Hz ±0.1Hz(battery mode) | ||||||||||||||
Waveform | Sinusoidal | ||||||||||||||
Power factor | 1.0 | ||||||||||||||
THDv | ≤2% (linear load), ≤5% (non-linear load) | ||||||||||||||
Crest factor | 3:1 | ||||||||||||||
Overload | 105% ~ 110% for 30 min, 110% ~ 130% for 10 min, 130% ~ 150% for 30 s, > 150% for 200 ms | ||||||||||||||
BATTERIES | |||||||||||||||
Battery type | Sealed lead acid maintenance free battery | ||||||||||||||
DC voltage | 24V(S) | 36V(S) | 36V(H) | 48V(S) | 72V(S) | 72V(H) | 72V(S) | 96V(S) | 96V(H) | ||||||
Inbuilt battery | 2×9Ah | 3×7Ah | / | 4×9Ah | 6×7Ah | / | 6×9Ah | 8×7Ah | / | ||||||
Charging current (max.) | Standard model: 1 A Long time model: 12 A (1~12A settable) | ||||||||||||||
Recharge time | Standard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery | ||||||||||||||
SYSTEM CONTROL AND COMMUNICATIONS | |||||||||||||||
Efficiency | ≥94.5% (Mainsmode) | ≥95.5% (Mainsmode) | ≥95.5% (Mainsmode) | ||||||||||||
≥89.5% (Batterymode) | ≥91.5% (Battery mode) | ≥91.5% (Battery mode) | |||||||||||||
≥97.5% (ECOmode) | ≥98.5% (ECOmode) | ≥98.5% (ECOmode) | |||||||||||||
Transfer time | Mains mode to battery mode: 0 ms Inverter mode to bypass mode: 4 ms (typical) | ||||||||||||||
Protections | Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection | ||||||||||||||
Communication port | RS232 (standard), USB / RS485 / SNMP/ dry contacts (optional) | ||||||||||||||
Display | LCD + LED | ||||||||||||||
ENVIRONMENT | |||||||||||||||
Operating humidity | 0 ~ 95 % RH @ 0 ~ 40°C (non-condensing) | ||||||||||||||
Storage temperature | -25°C ~ 55°C (exclude batteries) | ||||||||||||||
Operating altitude | ≤1000m, above 1000m, derating 1% for each additional 100 m | ||||||||||||||
IP rating | IP 20 | ||||||||||||||
Noise level at 1m | ≤ 50 dB | ||||||||||||||
OTHERS | |||||||||||||||
Dimensions (W × D × H) (mm) | 144×312×216 | 144×371× 216 | 144×312× 216 | 144×417×216 | 191×419× 335 | 144×417× 216 | 191×419×335 | 191×419× 335 | 144×417× 216 | ||||||
Packaged dimensions(W × D × H) (mm) | 230×402× 315 | 230×460× 315 | 230×402× 315 | 230×506×315 | 277×500× 435 | 230×506× 315 | 277×500×435 | 277×500× 435 | 230×506× 315 | ||||||
Net weight (kg) | 9.5 | 11.3 | 4.5 | 16.4 | 23.1 | 6.5 | 22.8 | 27.9 | 6.5 | ||||||
Gross weight (kg) | 10.5 | 12.3 | 5.5 | 17.9 | 24.6 | 8.0 | 24.3 | 29.4 | 8.0 |